TM 9-4120-425-14&P
LIQUID SIGHT INDICATOR
DIRECT SUPPORT MAINTENANCE REPLACEMENT - Continued
0075-00
INSTALLATION
1.
With a steady flow of dry nitrogen through refrigeration system, braze liquid sight indicator onto condenser coil and
tubing (See WP 0050-00 and WP 0051-00).
2.
Install condenser coil assembly (See WP 0078-00).
3.
Install filter-drier (See WP 0066-00).
4.
Leak test refrigeration system (See WP 0052-00).
5.
Evacuate refrigerant system (See WP 0053-00).
6.
Charge refrigerant system (See WP 0054-00).
7.
Install rear top panel (See WP 0019-00).
END OF TASK
0075-00-3
|