REFRIGERATION SYSTEM SERVICING (EVACUATION)
THIS WORK PACKAGE COVERS:
Service (Evacuation)
INITIAL SETUP:
Maintenance Level
Direct Support
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0118-00)
Tool Kit, Service, Refrigeration Unit (Item 2, Table 2, WP 0118-00)
Mask, Air Filtering (Item 29, Table 1, WP 0121-00)
Test Equipment
Vacuum pump (Item 3, Table 2, WP 0118-00)
Materials/Parts
Nitrogen (Item 4, Table 1, WP 0121-00)
References
Equipment Condition
Refrigerant system leak tested (WP 0052-00).
Refrigerant system discharged (WP 0049-00).
Main power source disconnected.
WARNING
Disconnect air conditioner power supply.
WARNING
Be sure that the manifold hoses are correctly connected. BLUE Hose = Low
Pressure, RED Hose = High Pressure.
CAUTION
Do not evacuate a leaking system. The vacuum created can cause air, moisture, and
dirt to enter system.
NOTE
Replace filter-dryer whenever refrigerant system is opened.
0053-00-1