TM 9-4120-425-14&P
CONDENSER COIL DIRECT SUPPORT MAINTENANCE REPLACEMENT
THIS WORK PACKAGE COVERS:
Removal, and Installation
INITIAL SETUP:
Maintenance Level
Direct Support
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0118-00)
Tool Kit, Service, Refrigeration Unit (Item 2, Table 2, WP 0118-00)
Recovery and Recycle Unit, Refrigerant, (Item 5, Table 2, WP 0118-00)
Mask, Air Filtering (Item 29, Table 1, WP 0121-00)
References
WP 0118-00 (MAC)
Equipment Condition
Mode selector switch in OFF position.
Main power source is disconnected.
Panels removed (WP 0019-00).
System refrigerant discharged (WP 0049-00).
Condenser motors and condenser impeller fans removed (WP 0062-00).
Condenser fan scrolls removed (WP 0063-00).
Condenser fan supports removed (WP 0064-00).
Damper actuator cylinder removed (WP 0068-00).
Test Equipment
Electronic refrigerant gas leak detector
Materials/Parts
Dry cleaning solvent (P-D 680) (Item 16, Table 1, WP 0121-00)
Nitrogen (Item 4, Table 1, WP 0121-00)
Brazing alloy (Item 5 or 6, Table 1, WP 0121-00)
Brazing flux (Item 7, Table 1, WP 0121-00)
Warm, soapy water
Brush, wire
Cloth, lint-free (Item 9, Table 1, WP 0121-00)
Oil (Item 14, Table 1, WP 0121-00)
Special Environmental Condition
NOTE
In accordance with Environmental Protection Agency regulations, refrigerants
cannot be discharged into the atmosphere. A refrigerant recovery and recycling unit
must be used whenever discharging the refrigerant system.
Operation of the recovery/recycling unit must be by AUTHORIZED PERSONNEL
ONLY.
0078-00-1
|