TM 9-4120-425-14&P
CONDENSER COIL DIRECT SUPPORT MAINTENANCE REPLACEMENT - Continued
0078-00
WARNING
Ensure power source is disconnected. Ensure refrigerant system is discharged.
REMOVAL
1.
Remove four screws (1), four lockwashers (2), four nuts (3), and gasket (4) attaching alternate power input
receptacle J1 (5) to housing.
2.
Move alternate power receptacle J1 (5) and wiring to aid in condenser coil removal.
3.
Remove two screws (6), two lockwashers (7), and mounting plate (8) attaching liquid sight indicator (9) to housing
(See WP 0075-00).
4.
Remove damper actuator cylinder (See WP 0068-00).
5.
Purge system (See WP 0050-00).
6.
Reposition electrical wiring away from piping area to be debrazed.
7.
Debraze condenser tube connections (See WP 0051-00).
8.
Debraze filter-drier (See WP 0066-00).
CAUTION
Use extreme care in removing condenser coil from housing to avoid damaging fins and coil piping.
0078-00-2
|