TM 9-4120-430-14
AIR CONDITIONER, COMPACT, HORIZONTAL
OPERATION UNDER USUAL CONDITIONS
INITIAL SETUP
References
Equipment Condition
Mode selector switch in OFF position
Correct voltage and phase power source (208 volts, three phase, 50/60 Hz for S9160-18KH-3 unit) or (230
volts, single phase, 50/60 Hz for S9150-18KH-1 unit)
Perform operator PMCS (WP 0010 00) as necessary
General Installation Site Requirements
A relatively level surface.
An unobstructed flow of air from outside the area.
An unobstructed flow of air from inside the conditioned area.
An unobstructed flow of air from outside the conditioned area to the fresh air intake.
STARTING AND OPERATING INSTRUCTIONS FOR COOLING
Starting
1.
Perform the preventive maintenance checks and services before operation.
CAUTION
When operating the S9150-18KH-1 unit on 50 cycles, the voltage must not exceed
220 volts. Operating at the 230 volt, 50 cycle, 1 phase power input may result in unit
shutdown over an extended period of time.  Compressor rating for 50 cycles
operation requires a maximum of 220 volts. The manufacturer recommends 208
volts be utilized during 50 cycles operation for the S9150-18KW-1 unit. Test results
have dictated this recommendation.
NOTE
The J2 connector is the main power input connecter. The J1 connector at the back of
the unit is the ALTERNATE input connector. To use the J1 ALTERNATE
connector, the TB1 connections must be shifted from J2 to J1. Refer to CONNECT
POWER SOURCE procedures in WP 0014 00 and to wiring schematic in WP 0038
2.
Check for correct voltage and phase at power source (208 volts, three phase, 50/60 Hz for S9160-18KH-3 unit) or
(230 volts, single phase, 50/60 Hz for S9150-18KH-1 unit).)
0005 00-1