TM 9-4120-430-14
DIRECT SUPPORT TROUBLESHOOTING PROCEDURES
AIR CONDITIONER, COMPACT, HORIZONTAL
THIS WORK PACKAGE COVERS:
Compressor Will Not Start, Compressor Starts But Stops At Once, Insufficient Cooling, Compressor Runs But
Does Not Cool, Compressor Excessively Noisy, Suction Pressure Too Low or Too High, Low Heat or No Heat
INITIAL SETUP:
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0067 00)
Tool Kit, Service, Refrigeration Unit (Item 2, WP 0067 00)
Recovery and Recycle Unit, Refrigerant (Item 5, WP 0067 00)
Mask, Air Filtering (Item 29, Table 1, WP 0069 00)
Test Equipment
Electronic refrigerant gas leak detector
References
Schematic Diagrams WP 0038 00
Personnel Required
One
Equipment Condition
Mode selector switch in OFF position
Main power source is disconnected
Top cover removed (WP 0018 00)
WARNING
Ensure power source is disconnected.
FAULT PROCEDURE 1. COMPRESSOR WILL NOT START.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
COMPRESSOR WILL NOT START
Step 1.
Make continuity check of control circuit and components. See WP 0038 00 for control circuit
schematic diagram.
a. Check for 24 volts at transformer (TR).
b. Check for power to K1 relay.
c. For S9150-18KH-1 unit, check continuity of B1 starter kit components (C3, C4, R1).
d. Repair loose or broken connections. Replace bad components. (Refer to WP 0026 00
through WP 0033 00).
Step 2.
If fans do not operate, make continuity check of circuit breaker. (Refer to WP 0027 00).
Replace bad circuit breaker. (Refer to WP 0027 00.)