TM 10-4110-262-13&P
0039 00
INSTALL
CAUTION
Ensure that no excess sealant enters into the refrigeration system.
Sealant may cause a restriction to the refrigeration system. Failure to
comply may result in damage to the equipment.
1. Apply a refrigerant-compatible thread sealer to the threads of the new switch.
2. Install and tighten the switch using a backup wrench. Reconnect the wires.
3. Pressurize the refrigeration system and test for leaks in accordance with WP 0031 00.
4. If no leaks are found, evacuate and charge the system in accordance with WP 0031 00.
5. Perform the refrigerator operation check in accordance with WP 0010 00 (PMCS No.7).
HPCO
END OF WORK PACKAGE