TM 10-4110-262-13&P
DIRECT SUPPORT MAINTENANCE
ADVANCED DESIGN REFRIGERATOR, 300 CUBIC FOOT (ADR-300)
REFRIGERATION UNIT HOT GAS SOLENOID VALVE
REMOVE/INSTALL, REPLACE
INITIAL SETUP
References
Tools and special tools
Refrigeration Unit Service (WP 0031 00)
Tool Kit, Refrigeration Service
PMCS (WP 0010 00)
Equipment Conditions
Materials and Parts
ADR-300 or RU disconnected from all power
Refrigerant R404A (WP 0068 00, Item 16)
supplies.
Compressor Oil (WP 0068 00, Item 5)
Solenoid Valve (WP 0059 00, Item 16)
Personnel Required
HVAC Technician (MOS 52C, AFSC 3E1x1) (1)
NOTE
The following procedures involve servicing the refrigeration system.
Some of these service procedures are regulated by Federal, and in some
cases, by State and Local laws. All regulated refrigeration service
procedures must be performed by an EPA certified technician, using
approved equipment and complying with all Federal, State and Local
laws.
NOTE
Replace the dehydrator whenever the high side is opened or when the
low side is opened for an extended period of time.
REMOVE
Solenoid Valve Coil
1. Remove the four screws from the solenoid valve coil.
2. Separate the two halves of the coil.
3. Gently pry the coil from the valve stem.
4. Refer to the install procedure to install the valve coil.