TM 10-4110-262-13&P
DIRECT SUPPORT MAINTENANCE
ADVANCED DESIGN REFRIGERATOR, 300 CUBIC FOOT (ADR-300)
REFRIGERATION UNIT HIGH PRESSURE CUT-OUT SWITCH
REPLACE
INITIAL SETUP
Personnel Required
Tools and special tools
HVAC Technician (MOS 52C, AFSC 3E1x1) (1)
Tool Kit, Refrigeration Service
References
Refrigeration System Service (WP 0031 00)
Materials and Parts
PMCS (WP 0010 00)
Refrigerant R404A (WP 0068 00, Item 16)
Compressor Oil (WP 0068 00, Item 5)
Equipment Conditions
High Pressure Cut-out Switch
No specified condition
Thread Sealer, Refrigerant
NOTE
The following procedures involve servicing the refrigeration system.
Some of these service procedures are regulated by Federal, and in some
cases, by State and Local laws. All regulated refrigeration service
procedures must be performed by an EPA certified technician, using
approved equipment and complying with all Federal, State and Local
laws. Failure to comply may cause damage to equipment
NOTE
Replace the dehydrator whenever the high side is opened or when the
low side is opened for an extended period of time.
REPLACE
1. Remove the condenser section front and top grilles.
2. Recover the refrigerant charge as outlined in WP 0031 00.
3. Disconnect the wires. Remove the defective switch using a backup wrench.
0039 00-1
|