TM 10-8145-222-23
0011
PMCS CONTINUED
Table 1. Maintainer Maintenance Preventative Maintenance Checks and Services (PMCS) Continued.
Item
Interval
Item To Be
Procedure
Equipment
No.
Checked or
Not Ready/
Serviced
Available If
8
1500
Electrical Box
a. Remove four screws (40) and washers (41) securing
Hours
(MTRCS01
electrical box cover (42) to electrical box (43), and
only)
remove cover (42).
b. Check electrical connections for looseness and tighten
Electrical
as needed.
connections
loose.
c.
Check electrical connections for discoloration indicating
Discoloration or
possible hidden corrosion. If found, tag and disconnect
corrosion
wiring; clean and reconnect as tagged.
found.
d. Check electrical connections and wiring for signs of
Signs of
overheating or arcing. Repair wiring as needed.
overheating or
arcing found.
e. Install cover (42) on electrical box (43) and secure using
Control box
four screws (40) and washers (41).
door not
closed.
f.
Control box
door not
closed.
0011-17