TM 10-8145-222-23
MAINTAINER MAINTENANCE
WATER PUMP V-BELT
REPLACE
INITIAL SETUP:
Tools and Special Tools
References
TM 10-8415-222-10
General Mechanic Tool Kit (WP 0096, Table 2, Item 5)
Tester, Belt Tension (TM 10-8415-222-10, Item 5)
Equipment Condition
TM 10-8145-222-23P
Refrigeration unit shut down and cooled for
30-minutes (TM 10-8415-222-10)
Personnel Required
External power cables disconnected (TM 10-8415-
222-10)
Quartermaster and Chemical Equipment Repairer
REPLACE
Remove
WARNING
Beware of V-belts and belt driven components. The refrigeration unit may start
automatically. Before performing maintenance on any belt driven system, make sure
that the power to the unit is off.
1. Open control panel access door (Figure 1, Item 1).
2. Place POWER ON/DOWN switch (Figure 1, Item 2) on control panel to DOWN position.
WARNING
Falling from the roof of the MTRCS can cause serious personal injury or death. Keep
three points of contact on the MTRCS at all times.
The refrigeration unit can start automatically causing drive components and fans to
operate unannounced. Unit operation must be prevented to avoid personal injury.
3. Access top of MTRCS using roof access provided.
.
Figure 1. POWER ON/DOWN Switch.