Figure 3. Exhaust Manifold.
REPLACE ­ CONTINUED

TECHNICAL MANUAL FOR MULTI-TEMPERATURE REFRIGERATED CONTAINER SYSTEM
Page Navigation
  382    383    384    385    386  387  388    389    390    391    392  
img
. . .
TM 10-8145-222-23
0039
REPAIR CONTINUED
11. Check that rain cap (Figure 3, Item 1) pivots freely.
12. Install top-right panel (WP 0013, Install).
13. Check that rain cap pivots freely with top-right panel installed.
14. Place emergency stop switch (Figure 2, Item 1) in PULL TO START position.
WARNING
Falling from the top of the MTRCS can result in serious injury or death to personnel.
Whenever performing maintenance on top of the MTRCS, always maintain three
points of contact to aid in stability. Never attempt to walk backwards while on top of
the container.
15. Climb off top of MTRCS using roof access.
16. Place POWER ON/DOWN switch (Figure 1, Item 2) to POWER ON position.
17. Close control panel access door (Figure 1, Item 1).
18. Place MTRCS back into desired mode of operation (TM 10-8415-222-10, Operating Procedures).
END OF TASK
REPLACE
1. Open control panel access door (Figure 1, Item 1).
2. Place POWER ON/DOWN switch (Figure 1, Item 2) on control panel to DOWN position.
3. Disconnect battery negative (-) terminal (WP 0053, Disconnect).
WARNING
Falling from the top of the MTRCS can result in serious injury or death to personnel.
Whenever performing maintenance on top of the MTRCS, always maintain three
points of contact to aid in stability. Never attempt to walk backwards while on top of
the container.
4. Access top of MTRCS using roof access.
5. Place emergency stop switch (Figure 2, Item 1) in PUSH TO STOP position.
6. Remove top-right panel (WP 0013, Remove).
0039-5