TM 10-8145-222-23
0049
REPLACE CONTINUED
21. On inside of container, carefully pull sensor (Figure 7, Item 5) and cable through until enough is through to
mount sensor on evaporator cover (Figure 7, Item 3).
22. Route sensor cable (Figure 7, Item 5) into evaporator (Figure 7, Item 8) through evaporator cutout on forward
side of evaporator.
23. Carefully pull return air sensor (Figure 7, Item 4) and temperature chart recorder sensor (Figure 7, Item 5)
through hole in cover (Figure 7, Item 3).
24. Mount return air sensor (Figure 7, Item 4) and temperature chart recorder sensor (Figure 7, Item 5) to cover and
secure with two tie wraps (Figure 7, Item 6).
25. Install tie wraps (Figure 7, Item 6) as needed from mount location forward to where sensor cables pass through
container wall while removing slack in cables as needed.
26. On outside of container, feed cable (Figure 6, Item 2) into bottom of temperature chart recorder (Figure 6,
Item 1) through waterproof protector (Figure 6, Item 3).
27. Feed cable through ferrite noise suppressor (Figure 4, Item 6) as shown in illustration (Figure 5).
28. Feed cable through feed through in hinged front panel side (Figure 4, Item 4).
29. Reconnect applicable sensor wiring (Figure 4, Item 5) as tagged.
30. Install tie wraps as needed to secure wiring (Figure 4, Item 5) inside hinged front panel (Figure 4, Item 4).
31. Install strain reliefs to sensor wires.
32. Remove two alignment screws (Figure 8, Item 1) mounted to side of rear cover (Figure 8, Item 2) and install into
opposite corners of chart recorder (Figure 8, Item 3).
33. Install rear cover (Figure 8, Item 2) to chart recorder (Figure 8, Item 3) and secure using 8 screws (Figure 8,
Item 4). Remove two alignment screws (Figure 8, Item 1) and store on side of rear cover (Figure 8, Item 2) and
install remaining 2 screws (Figure 8, Item 4).
34. Close hinged front panel (Figure 4, Item 2) and secure using two screws (Figure 4, Item 1).
35. Close chart recorder (Figure 6, Item 1) hinged front panel and secure using snap pin (Figure 6, Item 5).
36. Install tie wraps as needed to secure wiring (Figure 6, Item 2) between temperature chart recorder (Figure 6,
Item 1) and container pass through.
37. Close evaporator cover (Figure 7, Item 3) and secure using two bolts (Figure 7, Item 1) and washers (Figure 7,
Item 2).
38. Reconnect battery negative (-) terminal (WP 0053, Reconnect).
39. Place MTRCS back into desired mode of operation (TM 10-8415-222-10, Operating Procedures).
0049-10