TM 10-8145-222-23
MAINTAINER MAINTENANCE
DRAIN HOSES
REPLACE
INITIAL SETUP:
Tools and Special Tools
References
Service Refrigeration Ordnance
TM 10-8415-222-10
TM 10-8145-222-23P
Equipment Condition
Refrigeration unit shut down (TM 10-8415-222-10)
Personnel Required
External power cables disconnected (TM 10-8415-
Utilities Equipment Repairer
222-10)
REPLACE
Drain Hoses
WARNING
The drain hose heaters operate from high voltage sources. Make sure that power
cables are disconnected from the MTRCS and that the refrigeration unit is shut down
before performing maintenance on the unit. Failure to comply with this warning can
result in serious injury or death to personnel.
1. Disconnect battery negative (-) terminal (WP 0053, Disconnect).
NOTE
There are several individual drain hoses used between both evaporators to route
This task can be used to replace any drain hose. Some hoses may be secured to the
container using clamps and attaching hardware that will need to be removed as
required to remove the drain hose.
2. Disconnect both sides of damaged drain hose (Figure 1, Item 1).
3. Remove screws (Figure 1, Item 2), lock washers (Figure 1, Item 3), washers (Figure 1, Item 4), and clamps
(Figure 1, Item 5) securing drain hose (Figure 1, Item 1) as required. Discard lock washers.
4. Pull drain hose heater (Figure 1, Item 6) out of drain line.
5. Cut a single piece of clear hose to replace damaged piece.
6. Insert drain hose heater (Figure 1, Item 6) through new hose.
0050-1