Figure 4. Replace Relay.
Replace Transformer TR1

TECHNICAL MANUAL FOR MULTI-TEMPERATURE REFRIGERATED CONTAINER SYSTEM
Page Navigation
  868    869    870    871    872  873  874    875    876    877    878  
img
TM 10-8145-222-23
0084
REPAIR CONTINUED
2. Unplug and remove relay (Figure 4, Item 2) from relay socket (Figure 4, Item 3) by pulling upward on relay.
CAUTION
Use care when installing relay into the socket so as not to damage any relay
contacts.
3. Set dial setting of new relay to 85 and install replacement relay (Figure 4, Item 2) by plugging it into relay socket
(Figure 4, Item 3).
4. To replace relay socket (Figure 4, Item 3), first remove relay (Figure 4, Item 2).
5. Tag and disconnect wiring (Figure 4, Item 4) to socket (Figure 4, Item 3).
6. Remove two nuts (Figure 4, Item 5), two lock washers (Figure 4, Item 6), and two screws (Figure 4, Item 7)
securing socket (Figure 4, Item 3) to power box (Figure 4, Item 8).
7. Remove socket (Figure 4, Item 3).
8. Install replacement socket (Figure 4, Item 3) onto power box (Figure 4, Item 8) and secure using two screws
(Figure 4, Item 7), two new lock washers (Figure 4, Item 6), and nuts (Figure 4, Item 5).
9. Reconnect electrical wiring (Figure 4, Item 4) to socket (Figure 4, Item 3) as tagged.
10. Remove tags from wiring (Figure 4, Item 4).
11. Set dial setting of new relay to 85 and install relay (Figure 4, Item 1) into socket (Figure 4, Item 3).
12. Close power box door (Figure 4, Item 1).
0084-8