d. lnstallation. Replace a defective coil assembly
the air conditioner for repair or replacement. The
and install in reverse order of removal as illus-
coil is made of aluminum and is of the plate-fin
trated in figure 521. Evacuate and recharge re-
configuration.
frigerating system (para 5-33).
5-29. Condenser Coil
evaporator coil.
c. Cleaning, Inspection and Repair. Use a wire
bottom rear of the casing, directly beneath the
brush and brush off evaporator coil; blow dirt out
condenser fan. The coil must be removed from the
with compressed air. Wipe with cloth dampened
air conditioner for repair or replacement. The coil
with an approved cleaning solvent. Inspect coil for
is made from aluminum and is of the plate-fin con-
bent fins, damaged coil runs and interval leaks.
figuration.
straighten bent fins with needle nose pliers. A
damaged coil or an internally leaking coil cannot
condenser coil.
be repaired.