Click here to make tpub.com your Home Page

Page Title: Figure 513. One-tan thermostatic expansion valve, adjustment.
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

CAUTION. NEVER ADJUST THE EXPANSION VALVE UNLESS IT IS ABSOLUTELY NECESSARY. WHEN ADJUST-
ING THE EXPANSION VALVE. ALLOW AT LEAST 20 MINUTES BETWEEN EACH ADJUSTMENT. THIS
TlME ELEMENT IS VERY IMPORTANT AND MUST BE OBSERVED.
ADJUSTMENT
STEP 1. TAPE THE BULB OF A THE THERMOMETER TO SUCTION TUBE NEAR SENSING ELEMENT. INSULATE
THERMOMETER BULB.
STEP 2. INSTALL A SUITABLE PRESSURE GAGE AT SUCTION TUBE SERVICE VALVE (PAR. 5-20).
STEP 3.
MUST STABILIZE).
STEP 4. CHECK THERMOMETER AND PRESSURE GAGE READINGS. COMPARE READINGS WITH FIGURE 5-14
THERMOMETER READING SHOULD BE APPROXIMATELY 10 F HIGHER THAN TEMPERATURE
GIVEN ON FIGURE.
STEP 5. REMOVE BUTTON PLUG (SHOWN ABOVE). REMOVE CAP AND TURN ADJUSTING SCREW ONE
TURN CLOCKWISE TO INCREASE SUPERHEAT 4 F. OR ONE TURN COUNTERCLOCKWISE TO
DECREASE SUPERHEAT. INSTALL CAP. INSTALL BUTTON PLUG.
ME 4120 -222 -14/5-13
Figure 513. One-tan thermostatic expansion valve, adjustment.
AGO 20053A
50