TM 5-4120-356-14
Inspect fan motor for evidence of damage which would
(2) Inspection.
impair
serviceability.
(3) Test.
( a ) Check continuity of rotor windings for open windings or wind-
i n g s shorted to motor frame.
(b) Rotate motor shaft by hand to check for binding, indicating
w o r n bearings.
If worn bearings are indicated during inspection or test,
(4) Repair.
refer to figure 3-32 and repair motor.
( 5 ) R e p l a c e . R e p l a c e fan motor if serviceability is impaired by unre-
pairable damage, i f test indicates open windings, windings shorted to motor frame or
i f bearing damage is unrepairable.
(6)
Installation.
(a) Refer to figure 3-31 and install the fan motor.
(b) Refer to figure 3-30 and install the condenser fan and the
fan.
(c) Reinstall the air filter, evaporator air intake grille and the
c o n d e n s e r fan guard. (See figures 3-3 and 3-4.)
WIRING HARNESSES AND CONNECTORS.
WARNING
Disconnect the air conditioner from the
e l e c t r i c a l power source before attempt-
i n g to perform maintenance on the wir-
i n g harnesses or connectors.
W i r i n g Harnesses.
a.
(1)
Inspection
( a ) To gain access to the wiring harnesses, remove fabric cover,
t o p panel, condenser fan guard and lower access panel in accordance with paragraph
3-9.
( b ) Refer to paragraph 3-15b and remove the evaporator fan.
( c ) Refer to figure 3-12 and partially remove the junction box and
control box.
( d ) See figure 3-33 and remove pressure switch from enclosure.
( e ) See figure 3-22 and remove the RFI filter assembly from the
a i r conditioner to provide access to connector plugs P10 and P11.
( f ) Refer to figure 3-33 and inspect wiring harnesses for damage
w h i c h would impair serviceability.
|