( 3 ) T u r n thermostat control knob counter-clockwise to its limit.
( 4 ) O p e n c h a r g i n g cylinder outlet valve about two turns.
( 5 ) O p e n s u c t i o n pressure service valve slowly while observing the
s i g h t glass. When the bubbles disappear and the sight glass becomes clear, close
the suction pressure service valve.
( 6 ) Allow the air conditioner to continue to run for 10 minutes. If
bubbles reappear, add more refrigerant until bubbles again disappear. Continue this
A d d refrigerant a little at a time so that the
c y c l e until no more bubbles appear.
s y s t e m is not overcharged.
( 7 ) Turn selector switch to "OFF" position.
( 8 ) Refer to figure 4-5 and remove pressure gages and charging cylinder.
a .  General.
T h e compressor is a hermetically sealed unit and may not be
d i s a s s e m b l e d at the Direct Support Level.
Test.
b.
WARNING
D i s c o n n e c t the air conditioner from the
electrical power source before attmpt-
i n g to perform maintenance or testing of
t h e compressor.
( 1 ) T u r n s e l e c t o r s w i t c h t o the "OFF" position and disconnect the air
conditioner from the electrical power source.
( 2 ) R e f e r t o f i g u r e 3 - 1 2 a n d partially remove the junction box.
( 3 ) I f t h e c o m p r e s s o r i s o b v i o u s l y burned out, proceed with step c.
( 4 ) I f t h e c o m p r e s s o r i s i n o p e r a t i v e , but does not appear to be burned
o u t , r e f e r t o f i g u r e 3 - 2 8 ( w i r i n g d i a g r a m ) a n d t e s t t h e compressor wire harness for
( 5 ) R e p a i r o r r e p l a c e a n y b r o k e n w i r e s f o u n d and check for compressor
I f compressor now operates properly, no f u r t h e r maintenance action is
operation.
r e q u i r e d on the compressor.
(6) If no broken wires are found, or if compressor fails to operate
after broken wires are repaired or replaced, refer to table 4-1 and troubleshoot
t h e compressor.
(7) If troubleshooting fails to isolate and correct the problem, pro-
ceed to step c.
c. R e p l a c e .  R e p l a c e the compressor if burned out or if the compressor has
d a m a g e which would impair serviceability,  R e f e r t o s t e p d f o r r e m o v a l o f d e f e c t i v e