5-33. COMPRESSOR.-Continued
(4)
Braze
tube
connections
in
accordance
with
(Not  necessary
if
replaced
after
(5)  Replace  dehydrator.
refrigerant  system  cleaning  and  purging.)
(6)
Connect
P10
connector.
(7)  Leak
test
newly
connected
joints
and
all
connections
in
the
area.
(8)  (Models  F18H-3S  and  F18H-1S)
Install
top
rear  cover  (para
4-11).  (Models  F18H-3SA  and  F18H-3SB)
Install
top
cover  (para
(9)  Evacuate  and  charge  the  refrigeration
system
in
accordance  with  paragraphs  5-15  and  5-16.
5-34. TUBING AND FITTINGS.
The  refrigeration  system  contains  a  number  of  pieces  of  copper
tubing  in  a  variety  of  material  grades,  sizes,  lengths,  and  shapes,
and a number of elbows,  tees  and  adapters  in  several  sizes.
Observe  the  following  when  replacing  any  piece  of  tubing  or  fitting
in  the  system:
Be  sure  the  refrigeration  system  is  fully  discharged
and  purged,  and that dry nitrogen is flowing through
the  system  at  a  rate  of  1-2  cfm  (0.028  -  0.057
m 3 /minute)
Death or
before
brazing
or
debrazing.
injury  could  occur  from  exposure  to  refrigerant  gases
under  pressure.
Test/Replace.
a.
Replace  tubing  and  fittings  only  with
equal
material,
grade,
size,
length, and shape as the item removed.
Leak  test  the  entire  refrigeration  system  in  accordance  with
b.
paragraph 5-14 after any replacement action that required brazing.
c.
Replace  the  dehydrator  and  leak  test  the  dehydrator  flare
fittings  as  the  final  step  in  any  maintenance  action  that  required
the  refrigeration  pressure  system  to  be  opened.
d.
Evacuate
and  charge  the  refrigeration  system  in  accordance
5-15  and  5-16  after  all  other  maintenance  actions
are  completed.
5-84
Change 2

Privacy Statement - Press Release - Copyright Information. - Contact Us