|
|
TM
5-4120-386-14
Table 4-2. Organizational Troubleshooting-Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTWE ACTION
5. INSUFFICIENT HEATING-Continued
Step 7. Check that each heater element has approximately 115 Volts AC across
it. Disconnect power from unit. If heater element does not have 115
volts AC across it, check continuity of heater elements. (Refer to
If no continuity exists, replace heater elements.
(Refer to paragraph 4-33.)
Check that heater relay is energized and correct contacts are closed
Step 8.
when in HIGH HEAT mode using continuity tester and applying 30 volts
DC across Xl and 2X terminals. See schematic diagram.
Replace bad relay. (Refer to paragraph 4-25.)
Step 9. Check that output of rectifier is 24-28 volts DC when 30 volts AC is
applied across input terminals of rectifier.
Replace bad rectifier. (Refer to paragraph 4-28.)
Step 10. Check that output of transformer's 33-36 volts AC is applied across
input terminals of transformer.
Replace bad transformer. (Refer to paragraph 4-29.)
Check that continuity exists on heater cutout switch between
Step 11.
terminals 1 and 2, and elements 3 and 4.
Replace bad heater cutout switch.
(Refer to paragraph 4-32.)
4-18
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |