4120-01-238-4277">
|
|
TM 5-4120-393-14
5-21. Evaporator Coil
This task covers:
a. Removal
c. Installation
b. Replace
Initial setup.
Tools:
Tool kit, service, refrigeration unit NSN 5180-00-596-1474
Personnel: 2
Equipment condition:
1. Turn unit power off at power source. If there is a chance that it will be turned on, also disconnect power
cable to air conditioner.
2. Remove heater elements. See para 4-58.
3. Remove mist eliminator. See para 4-32.
4. Remove conditioned air filters. See para 4-30.
5. Remove right conditioned air inlet grille. See para 4-22.
General Safety Instructions:
WARNING
Disconnect input power to the air conditioner before performing any internal
maintenance. Voltages used can KILL. Shutting the unit off at the control panel
does not disconnect unit power.
When handling coils, wear gloves to avoid cuts and to reduce fin damage on the
coil.
NOTE
For inspection and cleaning of installed coil. See para 4-62.
REMOVAL
1.
Discharge the refrigerant system per para 5-9.
2.
Using a drill bit smaller than the rivet body, drill out the two rivets that secure the heater thermostat bracket.
3.
Remove the heater thermostat (S3) and bracket. See para 4-57.
4.
Using a screwdriver, remove the twelve screws (1) and washers (2) in the left hand (3) and right hand (4) channel
assembly and remove channels.
CAUTION
To prepare a joint on a valve for debrazing/brazing, disassemble the valve to the
extent possible, then wrap all but the joint with a wet rag to act as a heat sink.
5.
Remove grommet (5) from outlet evaporator tube.
5-50
|