DIRECT SUPPORT TROUBLESHOOTING PROCEDURES - Continued
0047-00
Table 1. Troubleshooting Procedures - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
Tighten loose connections.
11. LOW HEAT OR NO HEAT
1.
Check heater wiring and control
circuit for loose connections or
2.
Replace or repair broken wires.
broken wires.
Replace faulty switch. (Refer to WP
2.
Check continuity of mode
selector switch, temperature
selector switch and thermostat.
(Refer to WP 0034-00 and WP
Replace faulty heating elements.
3.
Disconnect and remove heater
(Refer to WP 0028-00.)
elements, and apply 115-volt AC
power to check for open circuit in
element or check resistance.
Element should heat.
Replace faulty switch. See WP 0027-
4.
Check continuity of two heater
cutout switches at room
temperature. Continuity should
exist. (Refer to WP 0027-00.)
Replace faulty relay. (Refer to WP
5.
Disconnect heater relay. Apply
24-28 volts to actuate relay and
check continuity at power
terminals. Continuity should
exist. (Refer to WP 0036-00.)
Repair or replace faulty fan or motor.
6.
Check operation of evaporator
(Refer to WP 0030-00.)
fan and motor. (Refer to WP
END OF TASK