|
|
TM 9-4120-430-14
OPERATOR TROUBLESHOOTING PROCEDURES
AIR CONDITIONER, COMPACT, HORIZONTAL
THIS WORK PACKAGE COVERS:
Air Conditioner Fails to Operate, Insufficient Cooling, No Heat or Low Heat
INITIAL SETUP:
Maintenance Level
Operator
FAULT PROCEDURE 1. AIR CONDITIONER FAILS TO OPERATE.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
AIR CONDITIONER FAILS TO OPERATE.
Step 1.
Verify that power cable is connected to proper voltage and phase with receptacle J2 or J1
ALTERNATE.
Connect power cable to receptacle. See WP 0038 00 schematic diagram.
NOTE
The J2 connector is the main power input connecter. The J1 connector at the back of
the unit is the ALTERNATE input connector. To use the J1 ALTERNATE
connector, the TB1 connections must be shifted from J2 to J1. Refer to CONNECT
POWER SOURCE procedures in WP 0014 00 and to wiring schematic in WP 0038
Step 2.
Verify that internal power connections are for power receptacle being used (J2 or J1 ALTERNATE).
See WP 0040 00 Schematic Diagram for proper power connection for power receptacle being
used.
Step 3.
Check to be sure that circuit breaker is on and the green POWER ON light is lit on the remote
control module.
Reset circuit breaker.
Step 4.
Make sure that mode selector switch is not in OFF position.
Turn selector knob to desired operation.
Step 5.
Check that high pressure switch has been reset.
Wait for the pressure switch to auto reset and for the compressor to start.
0009 00-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |