TM 9-4120-430-14
UNIT MAINTENANCE
AIR CONDITIONER, COMPACT, HORIZONTAL
CONDENSER AIR DISCHARGE LOUVER MAINTENANCE
REMOVAL, CLEANING, AND INSTALLATION
INITIAL SETUP:
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0067 00)
Materials/Parts
Dry Cleaning Solvent (Item 16, WP 0069 00
Personnel Required
One
Equipment Condition
Canvas cover detached (WP 0017 00)
Top cover removed (WP 0018 00)
WARNING
Ensure power source is disconnected.
REMOVAL
Condenser Guard
Remove condenser guard (1) by removing five screws (2), lockwashers (3), and flat washers (4). See figure 1.
Condenser Air Discharge Louver
1.
Remove five recessed screws (5) and two snap fastener cap screws (6) securing condenser air discharge louver (7) to
housing.
2.
Remove condenser air discharge louver (7) from housing by removing push-on nut (8) on pin of pivot arm (9) and
lifting louver linkage off pin of pivot arm (9).
CLEANING
Condenser Guard and Louver
1.
Straighten condenser guard bent frame.
WARNING
DRY CLEANING SOLVENT P-D-680
P-D-680 solvent vapors are toxic. Avoid prolonged or repeated breathing of vapors
or solvent contact with skin. Use only with adequate ventilation. Solvent is
flammable and should not be used near open flame. Fire extinguishers should be
readily available when solvent is used.
0021 00-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |