|
|
TM 9-4120-430-14
DIRECT SUPPORT MAINTENANCE
AIR CONDITIONER, COMPACT, HORIZONTAL
RECEIVER MAINTENANCE
REMOVAL AND INSTALLATION
INITIAL SETUP:
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0067 00)
Tool Kit, Service, Refrigeration Unit (Item 2, WP 0067 00)
Recovery and Recycle Unit, Refrigerant (Item 5, WP 0067 00)
Mask, Air Filtering (Item 29, Table 1, WP 0069 00)
Test Equipment
Electronic refrigerant gas leak detector (See TM 9-4940-509-14&P)
Materials/Parts
Nitrogen (Item 4, WP 0069 00)
Brazing alloy (Item 5 or 6, Table 1, WP 0069 00)
Brazing flux (Item 7, Table 1, WP 0069 00)
References
WP 0067 00 (MAC)
TM 9-4940-509-14&P
Personnel Required
One
Equipment Condition
Mode selector switch in OFF position.
Main power source is disconnected
Top cover removed (WP 0018 00)
Refrigerant system discharged (WP 0044 00)
System purged with nitrogen (WP 0045 00)
Related tube connections debrazed (WP 0046 00)
Special Environmental Condition
WARNING
REFRIGERANT-22 (R-22)
Unit contains R-22, a chemical substance which harms public health and the
environment by destroying ozone in the upper atmosphere, and that the
equipment is to be serviced by qualified personnel only.
Operation of the recovery/recycling unit must be by AUTHORIZED
PERSONNEL ONLY.
0053 00-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |