TM 10-8145-222-23
0018
REPLACE CONTINUED
14. Connect accumulator to filter-drier tube assembly (Figure 2, Item 6) to filter-drier (Figure 2, Item 3) and secure
with hex nut (Figure 2, Item 5). Tighten hex nut.
15. Connect condenser to filter-drier tube assembly (Figure 2, Item 2) to filter-drier (Figure 2, Item 3) and secure
with hex nut (Figure 2, Item 1). Tighten hex nut.
16. Tighten bolt (Figure 2, Item 8).
17. Perform leak check using soap/water solution.
18. Charge system with refrigerant as required (WP 0014, Service).
19. Install top-left panel (WP 0013, Install).
20. Place MTRCS back into desired mode of operation (TM 10-8145-222-10, Operating Procedures).
END OF TASK
END OF WORK PACKAGE
0018-5/6 blank