TM 10-8145-222-23
0032
REPLACE
Remove
WARNING
The JP-8 and diesel fuels used with the MTRCS are combustible and highly
explosive. Do not smoke or use open flame when performing maintenance. Flames
and explosion can occur resulting in severe injury or death.
The JP-8 and diesel fuels used with the MTRCS are toxic. Always wear eye, face,
and hand protection when working with or around fuel. If fuel contact is made with
eyes, flush your eyes and seek immediate medical attention. If fuel contact is made
with skin or clothing, remove contaminated clothing immediately, clean your skin with
a mild soap or cleanser, and rinse with clean water.
1. Open control panel access door (Figure 3, Item 1).
2. Place POWER ON/DOWN switch (Figure 3, Item 2) on control panel to DOWN position.
Figure 3. POWER ON/DOWN Switch.
3. Disconnect negative (-) battery cable from battery (WP 0053, Disconnect).
4. Disconnect electrical connector (Figure 4, Item 1) from EMI shield assembly (Figure 4, Item 2).
NOTE
Use care not to damage EMI shielding on cover.
5. Remove 18 screws (Figure 4, Item 3), lock washers (Figure 4, Item 4), and washers (Figure 4, Item 5) securing
EMI shield assembly (Figure 4, Item 2) to fuel tank (Figure 4, Item 6). Discard lock washers.