TM 10-8145-222-23
0032
REPLACE CONTINUED
8. Carefully place EMI shield assembly (Figure 5, Item 2) into place on fuel tank (Figure 5, Item 6). Do not install
attaching hardware at this time.
9. Connect electrical connector (Figure 5, Item 1) to EMI shield assembly (Figure 5, Item 2).
10. Connect battery negative (-) cable to battery (WP 0053, Reconnect).
11. Place POWER ON/DOWN switch (Figure 4, Item 2) on control panel to ON position.
NOTE
If testing is performed before installing cover, EMI signals will be emitted from pump.
12. Start refrigeration unit in diesel engine drive mode (TM 10-8415-222-10, Operating Procedures).
If no leaks are found, proceed to next step.
If a leak is detected, shut down refrigeration unit, clean up spillage and tighten loose connection fitting, re-
check for leaks, then proceed to next step.
13. Install 18 screws (Figure 5, Item 3), new lock washers (Figure 5, Item 4), and washers (Figure 5, Item 5) to
secure EMI shield assembly (Figure 5, Item 2) to fuel tank (Figure 5, Item 6).
14. Close control panel access door (Figure 4, Item 1).
15. Place MTRCS back into desired mode of operation (TM 10-8415-222-10, Operating Procedures).
END OF TASK
END OF WORK PACKAGE
0032-9/10 blank