Figure 3. Glow Plug Lead Assembly Test.
Figure 4. Glow Plug Lead Assembly Replacement.

TECHNICAL MANUAL FOR MULTI-TEMPERATURE REFRIGERATED CONTAINER SYSTEM
Page Navigation
  322    323    324    325    326  327  328    329    330    331    332  
img
. .
TM 10-8145-222-23
0033
TEST CONTINUED
10. Perform resistance check on each glow plug.
11. If resistance measured is not between 0.7 and 1.2 ohms, glow plug is faulty and must be replaced per this WP.
12. Reinstall glow plug lead assembly (Figure 3, Item 2) onto each glow plug (Figure 3, Item 3), electrical lead
(Figure 1, Item 4), and secure using three nuts (Figure 3, Item 1) onto cylinder head (Figure 3, Item 5).
13. Place emergency stop switch (Figure 2, Item 1) on PULL TO START position.
14. Install top-right panel (WP 0013, Install).
WARNING
Falling from the top of the MTRCS can result in serious injury or death to personnel.
Whenever performing maintenance on top of the MTRCS, always maintain three
points of contact to aid in stability. Never attempt to walk backwards while on top of
the container.
15. Climb off top of MTRCS using roof access provided.
16. Reconnect battery (WP 0053, Reconnect).
17. Place POWER ON/DOWN switch (Figure 1, Item 2) on control panel to ON position.
18. Operate MTRCS to verify proper operation (TM 10-8415-222-10, Operating Procedures).
19. Place MTRCS back into desired mode of operation (TM 10-8415-222-10, Operating Procedures).
END OF TASK
REPLACE
WARNING
The exhaust system will become extremely hot after a short period of operating time.
Allow engine to cool for 30 minutes before performing maintenance.
1. Open control panel access door (Figure 1, Item 1).
2. Place POWER ON/DOWN switch (Figure 1, Item 2) on control panel to DOWN position.
WARNING
Falling from the top of the MTRCS can result in serious injury or death to personnel.
Whenever performing maintenance on top of the MTRCS, always maintain three
points of contact to aid in stability. Never attempt to walk backwards while on top of
the container.
3. Access top of MTRCS using roof access provided.
0033-4