TM 10-8145-222-23
0060
REPLACE CONTINUED
NOTE
The ground wires for connectors 1CP and 2CP are attached to single shared ground
with a screw and a nut.
13. Tag and disconnect evaporator connector 1CP (Figure 6, Item 1) and green ground wire (Figure 6, Item 2) from
frame.
14. Tag and disconnect evaporator connector 2CP (Figure 6, Item 3) and green ground wire (Figure 6, Item 2) from
frame.
Figure 6. 1CP and 2CP Electrical Connectors.
NOTE
The two evaporator cables and associated connectors 1CP and 2CP will be fed
through a hole in the back of the refrigerator unit during removal, with refrigeration
lines.
15. Cut wire ties as needed to free evaporator electrical cables from refrigerant piping.
16. Feed both evaporator electrical cables out so that they hang on top of MTRCS roof toward right side.
WARNING
Soldering procedures emit gasses that can be harmful if inhaled for long durations.
Before performing any soldering procedures, make sure that adequate ventilation is
available. Use face shield and protective gloves when performing soldering
procedures.
17. Remove all insulation covering 1 1/8-inch refrigerant pipe (Figure 7, Item 3).