thermostatic expansion valve adjusta in the same
operation. The one-half ton thermostatic expan-
manner.
sion valve functions when the unit is in the bypass
cycle of operation. Each expansion valve is pro-
d. Installation. Replace defective expansion
vided with a super heat setting adjustment (10F.
valves and install in reverse order of removal as
for each model) to assure efficiency in the refrig-
illustrated in figure 5-12. Evacuate and recharge
erant system.
the unit refrigerating system (para 5-33).
b. Removal. Discharge the refrigerant system,
refer to figure 5-12, and remove the themostatic
Note. A gas is superheated whenever its temperature is
expansion valves.
higher than the temperature, corresponding to its pressure
at saturation. Example: Refrigerant -22 at 69 pounds
c. Adjustment. Refer to figures 5-13 and 5-14,
pressure has a temperature of 40" F. If the suction pres-
and check and adjust the superheat setting of the
sure gage reads 69 pounds and the temperature of the
suction tube reads 50F., the gas is superheated 10F.
1-ton thermostatic expansion valve, The  1/2-ton