TM 5-4120-356-14
f. Installation
(1) Refer to paragraph 4-14d and install a new dehydrator.
(2) Refer to figure 4-6 and install a new compressor.
(3) Refer to paragraph 4-4c and check the system for refrigerant leaks. If any leaks are found, refer to
(4) Reconnect plug P3 to J3 on junction box (see figure 3-12), and install junction box.
(6) Refer to figure 4-4 and evacuate the refrigerant system.
(6) Refer to paragraph 4-10 and charge the system with refrigerant. Leave the pressure gages connected.
(7) With the unit operating in the cooling mode, check pressures. For proper discharge and suction lines
pressure, see Table 4-1.1.
(8) If pressures are satisfatory, close all valves, remove gages and turn the selector switch to the "OFF"
position. If pressures are unsatisfactory, refer to Table 4-1-2.
Table 41.1. Troubleshooting
NORMAL TEMPERATURE-PRESSURE RELATIONSHIPS
95F (36C) dry bulb return air to unit
100F
110F
125F
Outdoor ambient
50F
75F
43.5C
10C
24C
38C
52C
temperature
Gauge Pressures
65-75
70-80
75-90
56-65
Suction (psig)
56-60
(Kg/CM2)
4.92-5.62
4.57-5.27
5.27-6.33
3.93-4.22
3.93-4.57
275-295
400-420
185-205
375-380
Discharge (psig)
135-155
(Kg/CM2)
28.12-29.53
9.50-10.90
13.00-14.41
19.33-20.74
26.36-26.72
80F (27C) dry bulb return air to unit
100F
125F
50F
75F
Outdoor ambient
52C
10C
24C
38C
temperature
Gauge Pressures
Suction (psig)
56 min.
56 min.
56-65
65-75
(Kg/CM2)
4.27-5.27
3.93 min.
3.93 min.
3.93-4.57
Discharge (psig)
130-150
180-200
270-290
290-410
(Kg/CM2)
9.14-10.55
12.65-14.06
18.98-20.39
20.39-28.82
NOTE: Dry bulb temperatures are measured with an ordinary thermometer
Change 3 4-22.1
|