TM 10-8145-222-23
0052
REPLACE CONTINUED
NOTE
There are three ground wires attached to the power box GND; one for cable
assembly P1A ground, one for cable assembly P2A ground, and one for standby
motor ground. Only one of the wires is applicable to cable assembly P1A and will
have to be removed to accomplish removal of cable assembly P1A. The other two
ground wires will remain inside the power box and be re-connected when cable
assembly P1A is re-installed.
9. Tag one white ground wire and two green ground wires terminating at power box ground lug (Figure 9, Item 6)
on power box (Figure 9, Item 4).
10. Loosen three terminal screws (Figure 9, Item 5) and disconnect three wires from switch S1 (Figure 9, Item 2)
terminals S1-1, S1-5, and S1-9 (Figure 2).
NOTE
There are two white neutral wires attached to terminal TR1-X0. One of the ground
wires is for cable P1A and one of the ground wires is for cable P2A.
11. Loosen terminal screw and disconnect two white neutral wires from transformer TR1 (Figure 9, Item 3) terminal
TR1-X0 (Figure 3).
12. Remove power box ground lug (Figure 9, Item 6), lock washer (Figure 9, Item 7), washer (Figure 9, Item 8), and
screw (Figure 9, Item 9) securing three ground wires to power box (Figure 9, Item 4). Discard lock washer.
13. Disconnect three ground wires from power box (Figure 9, Item 4).
NOTE
When removing the wiring for cable assembly P1A from the power box, make note of
how wires are routed and where tie-down straps are removed from in order to aid in
the re-installation of the cable assembly.
14. Carefully cut and remove any tie-down straps securing cable assembly P1A (Figure 9, Item 10) wires together
with other wires.
15. Loosen locking nut (Figure 9, Item 11) securing cord mesh (Figure 9, Item 12) and cable assembly P1A
(Figure 9, Item 10) to power box (Figure 9, Item 4).
16. Remove locking nut (Figure 9, Item 11) securing cable assembly (Figure 9, Item 10) to power box (Figure 9,
Item 4).
17. Carefully guide P1A wiring out of power box (Figure 9, Item 4) to fully remove cable assembly P1A (Figure 9,
Item 10).
NOTE
The cord mesh surrounding the cable can be easily maneuvered and slid up or down
the cable by compressing the mesh.
18. Slide cord mesh (Figure 9, Item 12) back along length of cable by compressing cord mesh.
0052-12