TM 10-8145-222-23
0052
REPLACE CONTINUED
NOTE
There are two white neutral wires attached to terminal TR1-X0. One of the ground
wires is for cable P1A and one of the ground wires is for cable P2A.
11. Loosen terminal screw and disconnect two white neutral wires from transformer TR1 (Figure 10, Item 3)
terminal TR1-X0 (Figure 3).
12. Remove one power box ground lug (Figure 10, Item 6), lock washer (Figure 10, Item 7), washer (Figure 10,
Item 8), and screw (Figure 10, Item 9) securing three ground wires to power box (Figure 10, Item 4). Discard
lock washer.
13. Disconnect three ground wires from power box (Figure 10, Item 4).
NOTE
When removing the wiring for cable assembly P2A from the power box, make note of
how wires are routed and where tie-down straps are removed from in order to aid in
the re-installation of the cable assembly.
14. Carefully cut and remove any tie-down straps securing cable assembly P2A (Figure 10, Item 10) wires together
with other wires.
15. Loosen locking nut (Figure 10, Item 11) securing cord mesh (Figure 10, Item 12) and cable assembly P2A
(Figure 10, Item 10) to power box (Figure 10, Item 4).
16. Slide cord mesh (Figure 10, Item 12) back along length of cable.
17. Remove locking nut (Figure 10, Item 11) securing cable assembly (Figure 10, Item 10) to power box (Figure 10,
Item 4).
18. Carefully guide P2A wiring out of power box (Figure 10, Item 9) to fully remove cable assembly P2A (Figure 10,
Item 10).
NOTE
The cord mesh surrounding the cable can be easily maneuvered and slid up or down
the cable by compressing the mesh.
19. Slide cord mesh (Figure 10, Item 12) back along length of cable by compressing cord mesh.
20. Remove locking nut (Figure 10, Item 11) and cord mesh (Figure 10, Item 12) for re-installation on replacement
cable assembly P2A (Figure 10, Item 10) by compressing cord mesh allowing it to slide easily along cable.
21. Remove grommet (Figure 10, Item 13).
0052-16