Figure 3. 7/8-Inch Refrigerant Pipe Saddle Clamp.
Steps 34 and 35 are for compartment 2 (aft) evaporator only.

TECHNICAL MANUAL FOR MULTI-TEMPERATURE REFRIGERATED CONTAINER SYSTEM
Page Navigation
  808    809    810    811    812  813  814    815    816    817    818  
img
.
TM 10-8145-222-23
0080
REPLACE CONTINUED
30. Pull any insulation away from piping as needed for better access. Retain for reinstallation.
31. Cut 3/8-inch refrigerant pipe (Figure 4, Item 3) at cut location (Figure 4, Item 4) midway between solenoid valve
mount bracket and cutout in evaporator.
32. Cut 1/2-inch refrigerant pipe (Figure 4, Item 1) at cut location (Figure 4, Item 2) midway between solenoid valve
mount bracket and cutout in evaporator.
33. Remove grommet (Figure 4, Item 5) on rear of evaporator near 3/8-inch and 1/2-inch refrigerant pipes.
Figure 4. 1/2-Inch and 3/8-Inch Refrigerant Pipes.
0080-6