TM 10-8145-222-23
MAINTAINER MAINTENANCE
POWER CABLE ASSEMBLIES
REPAIR
INITIAL SETUP:
Tools and Special Tools
References
Electrical Connector Kit (WP 0096, Table 2, Item 3)
TM 10-8415-222-10
Service Refrigeration Ordnance
TM 10-8145-222-23P
Equipment Condition
Materials/Parts
Lock Washer, 3/8-in ID (WP 0111, Item 13)
Refrigeration unit shut down (TM 10-8415-222-10)
External power cables disconnected (TM 10-8415-
222-10)
Personnel Required
Utilities Equipment Repairer (2)
REPAIR
WARNING
The MTRCS contains high voltage sources and exposed rotating parts. Make sure
that power cables are disconnected from the power source and that the refrigeration
unit is shut down before performing maintenance on the unit. Failure to comply with
this warning can result in serious injury or death to personnel.
NOTE
The gland nut is left-hand threaded.
When replacing pins, all pins must be replaced. Do not replace single pins.
1. Loosen gland nut (Figure 1, Item 1).
NOTE
Compress cable grip to slide it back.
2. Slide gland nut (Figure 1, Item 1), cable grip (Figure 1, Item 2), gland (Figure 1, Item 3), and gland washer
(Figure 1, Item 4) back along cable.
3. Remove three hex screws (Figure 1, Item 5) and three lock washers (Figure 1, Item 6) from back adapter
(Figure 1, Item 7). Retain lock washers.
4. Slide back adapter (Figure 1, Item 7) back along cable.
5. Remove pin spacer assembly (Figure 1, Item 8), with contacts (Figure 1, Item 9) installed, from shell and
coupling nut assembly (Figure 1, Item 12).
6. Tag wires (Figure 1, Item 11).
0085-1