TM 5-4120-356-14
T a b l e 4-1. Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
INSUFFICIENT COOLING (continued)
I f adding refrigerant to the system does not clear up bubbles in
Step 2.
the sight glass, there may be air in the system.
O p e n system and remove
refrigerant (figure 4-2). Purge the
s y s t e m in accordance with
paragraph 4-8, evacuate the system
( f i g u r e 4-4) and recharge
the system with refrigerant in
a c c o r d a n c e with paragraph
Step 3.
Check for inoperative fans.
Perform corrective actions listed in section 10 of this
troubleshooting table.
Step 4.
Check air conditioner operating pressures for excessive refriger-
ant in the system in accordance with paragraph 4-12f.
R e l e a s e excess refrigerant from the system until the proper
charge is attained (figure 4-2).
Step 5.
Inspect expansion valve and check superheat (paragraph 4-14j).
R e p a i r or r e p l a c e d a m a g e d o r d e f e c t i v e e x p a n s i o n v a l v e . A d j u s t
expansion v a l v e i f s u p e r h e a t i s n o t c o r r e c t i n a c c o r d a n c e w i t h
I n s p e c t quench v a l v e and check superheat (paragraph 4-14k).
Step 6.
R e p a i r or r e p l a c e d a m a g e d o r d e f e c t i v e q u e n c h v a l v e . A d j u s t
quench valve if superheat is not correct in accordance with
Step 7.
Inspect and test pressure equalizer solenoid valve in accordance
with paragraph 3-13a.
R e p a i r or replace damaged or defective solenoid valve in
a c c o r d a n c e with paragraph 4-14c.
Inspect and test liquid line solenoid valve in accordance with
Step 8.
R e p a i r or replace damaged or defective solenoid valve in
a c c o r d a n c e with paragraph 4-14b.