TM 5-4120-356-14
T a b l e 4-1. Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
COMPRESSOR WILL NOT START (continued)
Inspect and test selector switch (paragraph 3-10b).
Step 5.
Replace damaged or defective selector switch.
Step 6.
Inspect and test compressor relay (paragraph 3-10h).
R e p l a c e damaged or defective compressor relay.
Step 7.
Inspect and test time delay relay (paragraph 3-10j).
Replace damaged or defective time delay relay.
Step 8.
Inspect for loose electrical connections and defective wiring
connections. Repair or replace defective wiring.
Tighten
loose
Inspect and test high and low pressure cut-out switches (paragraph
Step 9.
2. COMPRESSOR
SHORT
CYCLES
Check air conditioner operating pressures for excessive refriger-
Step 1.
ant in system (paragraph 4-12f).
R e l e a s e excessive refrigerant from system until the proper
charge is attained (figure 4-2).
Step 2.
Inspect and test liquid line solenoid valve (paragraph 3-13a).
Repair or replace damaged or defective solenoid valve (para-
graph 4-14b).
Inspect and test pressure equalizer solenoid valve (paragraph 3-
Step 3.
Repair or replace damaged solenoid valve (paragraph 4-14c).
3.
INSUFFICIENT COOLING
Check for insufficient refrigerant in system (bubbles in sight
Step 1.
glass).
Add refrigerant (paragraph 4-11).
4-2
|