T a b l e 4-1. Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
INSUFFICIENT COOLING (continued)
Clogged dehydrator (drier)
Step 9.
R e p l a c e dehydrator in accordance with paragraph 4-14d.
Step 10. Restriction in liquid line.
Open system and remove refrigerant (figure 4-2). Purge system
in accordance with paragraph 4-8. Evacuate system (figure 4-4)
a n d recharge the system with refrigerant in accordance with
REFRIGERANT SYSTEM CONTINUOUSLY LOSING REFRIGERANT
4.
Step 1.
Check refrigerant tubing and components for leaks in accordance
with paragraph 4-4c.
Repair leaks if possible in accordance with paragraph 4-4d.
Replace unrepairable tubing or components.
Step 2.
Check for defective relief valve in accordance with paragraph 4-14g.
Replace defective pressure relief valve.
5. AIR CONDITIONER NOISY DURING OPERATION
Step 1.
Check air conditioner operating pressures for excessive refriger-
ant in the system in accordance with paragraph 4-12f.
R e l e a s e excess refrigerant from the system until the proper
charge is attained (see figure 4-2).
Step 2.
Check for noisy compressor, indicating worn bearings or insuffic-
ient clearance between rotating parts.
R e p l a c e compressor in accordance with procedures given in
Step 3.
I n s p e c t expansion valve and check superheat in accordance with
Repair or replace damaged or defective expansion valve. Adjust
expansion valve if superheat is not correct in accordance with
4-4
|