TM 10-8145-222-23
MAINTAINER MAINTENANCE
THERMAL WATER TEMPERATURE RESISTOR
REPLACE
INITIAL SETUP:
Tools and Special Tools
References
General Mechanic Tool Kit (WP 0096, Table 2, Item 5)
TM 10-8415-222-10
Personnel Required
TM 10-8145-222-23P
Quartermaster and Chemical Equipment Repairer
Equipment Condition
Refrigeration unit shut down (TM 10-8415-222-10)
External power cables disconnected (TM 10-8415-
222-10)
REPLACE
1. Open control panel access door (Figure 1, Item 1).
2. Place POWER ON/DOWN switch (Figure 1, Item 2) on control panel to DOWN position.
WARNING
Falling from the roof of the MTRCS can cause serious personal injury or death. Keep
three points of contact on the MTRCS at all times.
The refrigeration unit can start automatically causing drive components and fans to
operate unannounced. Unit operation must be prevented to avoid personal injury.
3. Access top of MTRCS using roof access provided.