TM 10-8145-222-23
MAINTAINER MAINTENANCE
REPLACE, ADJUST
INITIAL SETUP:
Tools and Special Tools
References
TM 10-8415-222-10
Refrigeration Equipment
Tool Kit (supplement) (WP 0096, Table 2, Item 7)
Service Refrigeration Ordnance
TM 10-8145-222-23P
Tester, Belt Tension (TM 10-8415-222-10, Item 5)
Equipment Condition
Personnel Required
Refrigeration unit shut down (TM 10-8415-222-10)
Utilities Equipment Repairer
External power cables disconnected (TM 10-8415-222-
10)
REPLACE
WARNING
Metal jewelry will conduct electricity. Remove all jewelry when working on equipment.
Failure to comply can cause injury or death to personnel by electrocution.
Beware of V-belts and belt driven components. The refrigeration unit may start
automatically. Before performing maintenance on any belt driven system, make sure
that the power to the unit is off.
1. Open control panel access door (Figure 1, Item 1).
2. Place POWER ON/DOWN switch (Figure 1, Item 3) on control panel to DOWN position.
3. Disconnect negative (-) battery terminal (WP 0053, Disconnect).
4. Remove compressor to standby motor V-belt (WP 0036, Remove).
WARNING
Falling from the top of the MTRCS can result in serious injury or death to personnel.
Whenever performing maintenance on top of the MTRCS, always maintain three
points of contact to aid in stability. Never attempt to walk backwards while on top of
the container.
5. Access top of MTRCS using roof access provided.
0035-1