TM 10-8145-222-23
MAINTAINER MAINTENANCE
REPAIR, REPLACE
INITIAL SETUP:
Tools and Special Tools
References
TM 10-8415-222-10
Refrigeration Equipment
Tool Kit (supplement) (WP 0096, Table 2, Item 7)
Service Refrigeration Ordnance
TM 10-8145-222-23P
Equipment Condition
Materials/Parts
Refrigeration unit shut down (TM 10-8415-222-10)
External power cables disconnected (TM 10-8415-
Gasket Kit and Seal (WP 0111, Item 3)
222-10)
Personnel Required
Utilities Equipment Repairer
REPAIR
WARNING
The refrigeration unit can start automatically causing drive components and fans to
operate unannounced. Unit operation must be prevented to avoid personal injury.
Falling from the roof of the MTRCS can cause serious personal injury or death. Keep
three points of contact on the MTRCS at all times.
3. Tag and disconnect electrical connector from valve coil (Figure 1, Item 1).
4. Spread clip (Figure 1, Item 2) securing coil (Figure 1, Item 3) to valve outer body (Figure 1, Item 4) and remove
coil.
0063-1