TM 10-8145-222-23
0066
REPLACE CONTINUED
Figure 5. Suction Service Valve Assembly Installation.
34. Tighten four suction service valve mount bolts (Figure 5, Item 16) to 55 to 80 foot-pounds of torque (WP 0091).
35. Install clamp (Figure 5, Item 15) onto CPR valve (Figure 5, Item 5) and secure to clamp mounting plate using
one screw (Figure 5, Item 11), new lock washer (Figure 5, Item 12), washer (Figure 5, Item 13), and nut
(Figure 5, Item 14).