TM 10-8145-222-23
0088
REPAIR CONTINUED
8. Remove capacitor (Figure 1, Item 6).
9. Install replacement capacitor (Figure 1, Item 6) into capacitor box (Figure 1, Item 8) and secure in place using
capacitor box frame mounting strap and hex nut (Figure 1, Item 7). Tighten nut.
10. Reconnect electrical connections (Figure 1, Item 5) to capacitor (Figure 1, Item 6) as tagged. Remove tags.
11. Install capacitor box cover (Figure 1, Item 4) with gasket (Figure 1, Item 9) and secure using four bolts
(Figure 1, Item 1), flat washers (Figure 1, Item 2), and nylon washers (Figure 1, Item 3).
12. Connect battery negative (-) terminal (WP 0053, Reconnect).
13. Operate refrigeration unit in accordance with normal operating procedures to verify proper operation after
replacement of capacitors (TM 10-8415-222-10, Operating Procedures).
14. Place MTRCS into desired mode of operation (TM 10-8415-222-10, Operating Procedures).
Figure 1. Capacitor Box.