TM 10-8145-222-23
0020
REPLACE CONTINUED
Figure 1. Compressor Discharge Temperature Sensor.
Suction Pressure Transducer
WARNING
Falling from the roof of the MTRCS can cause serious personal injury or death. Keep
three points of contact on the MTRCS at all times.
1. Disconnect electrical connector (Figure 2, Item 1) from suction pressure transducer (Figure 2, Item 2).
CAUTION
Remove only the suction pressure transducer.
NOTE
The suction pressure transducer has an internal Schrader valve that will prevent
refrigerant from escaping the compressor when the transducer is removed.
2. Unscrew suction pressure transducer (Figure 2, Item 2) from Schrader valve (Figure 2, Item 3).