TM 10-8145-222-23
0020
REPLACE CONTINUED
NOTE
Disconnecting the starter solenoid wire and allowing the diesel engine to fail at an
attempted start will cause the run relay to de-energize.
4. Disconnect starter solenoid wire (Figure 3, Item 1) from starter (Figure 3, Item 2).
Figure 3. Starter Solenoid Wire.
5. Attempt to start refrigeration unit in diesel engine drive mode (TM 10-8145-222-10, Operating Procedures).
Engine will fail to start and cause run relay to de-energize.
WARNING
Falling from the roof of the MTRCS can cause serious personal injury or death. Keep
three points of contact on the MTRCS at all times.
6. Access top of MTRCS using roof access provided.
7. Connect electrical connector (Figure 2, Item 1) to new suction pressure transducer (Figure 2, Item 2), but do not
8. Climb off of MTRCS using roof access provided.
9. On microprocessor display panel (Figure 4, Item 1), press UNIT DATA key (Figure 4, Item 2) until SUCT (or
CD1 if using coded display) is shown in display (Figure 4, Item 3). Immediately press and hold ENTER key
(Figure 4, Item 4) for three seconds.
Display should read 0. If display does not read 0, press and hold ENTER key for three seconds again. If
display still does not read 0, replace suction pressure transducer.