Figure 3. Starter Solenoid Wire.
Compressor Discharge Temperature Sensor

TECHNICAL MANUAL FOR MULTI-TEMPERATURE REFRIGERATED CONTAINER SYSTEM
Page Navigation
  240    241    242    243    244  245  246    247    248    249    250  
img
. .
TM 10-8145-222-23
0020
REPLACE CONTINUED
Figure 4. Microprocessor Controller Display.
10. Access top of MTRCS using roof access provided.
11. Reconnect starter solenoid wire (Figure 3, Item 1) onto starter (Figure 3, Item 2).
12. Install calibrated suction pressure transducer (Figure 2, Item 2) into compressor (Figure 2, Item 3).
13. Reconnect electrical connector (Figure 2, Item 1) to suction pressure transducer (Figure 2, Item 2).
14. Install top-middle panel (WP 0013, Install).
15. Raise front panel assembly access cover (Figure 2, Item 5) and secure to front panel assembly using four
quarter-turn fasteners (Figure 2, Item 4).
END OF TASK
0020-5