• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
Figure 1. Compressor Discharge Temperature Sensor.
Figure 3. Starter Solenoid Wire.

TECHNICAL MANUAL FOR MULTI-TEMPERATURE REFRIGERATED CONTAINER SYSTEM
Page Navigation
  238    239    240    241    242  243  244    245    246    247    248  
img
.
TM 10-8145-222-23
0020
REPLACE CONTINUED
Figure 2. Suction Pressure Transducer.
NOTE
Before installing the replacement suction pressure transducer, it must be calibrated.
Calibration of the suction pressure transducer cannot be accomplished if the run
relay is energized. The following steps will allow you to calibrate the transducer while
the run relay is de-energized.
Calibration of the transducer must be accomplished at atmospheric pressure (0.0
psig or 14.7 psia). If the sensor reading is greater than 20 psig (34.7 psia) or less
than -6.7 psig (8 psia), the transducer cannot be calibrated.
3. Rotate four quarter-turn fasteners (Figure 2, Item 4) securing front panel assembly access cover (Figure 2,
Item 5) closed and lower cover.
0020-3


Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved.