TM 10-8145-222-23
MAINTAINER MAINTENANCE
COMPRESSOR SENSORS
REPLACE, TEST
INITIAL SETUP:
Tools and Special Tools
Personnel Required
Utilities Equipment Repairer
References
Refrigeration Equipment
TM 10-8145-222-10
Tool Kit (supplement) (WP 0096, Table 2, Item 7)
Service Refrigeration Ordnance
TM 10-8145-222-23P
Materials/Parts
Equipment Condition
Refrigeration unit shut down (TM 10-8145-222-10)
Top-middle panel and right side removed (WP 0013)
REPLACE
Compressor Discharge Temperature Sensor
WARNING
Falling from the roof of the MTRCS can cause serious personal injury or death. Keep
three points of contact on the MTRCS at all times.
1. Disconnect electrical connector (Figure 1, Item 1) from Compressor Discharge Temperature (CDT) sensor
(Figure 1, Item 2). Cut tie wraps as necessary.
2. Remove CDT sensor (Figure 1, Item 2) from compressor (Figure 1, Item 3).
3. Install new CDT sensor (Figure 1, Item 2) to compressor (Figure 1, Item 3).
4. Reconnect electrical connector (Figure 1, Item 1) to CDT sensor (Figure 1, Item 2). Install tie wraps as
necessary.
5. Install top-middle panel (WP 0013, Install).
0020-1